Authentic Huawei H19-371_V1.0 Exam Dumps PDF - Feb-2023 Updated H19-371_V1.0 Dumps Special Discount for limited time Try FOR FREE NEW QUESTION 260 Regarding the micro-module and fire protection system, which of the following are true? (multiple choice) A. The data center fire host provides passive dry contact signals to the ECC800, and the ECC800 can identify the fire alarm information B. ECC800 can [...]

Authentic Huawei H19-371_V1.0 Exam Dumps PDF - Feb-2023 Updated [Q260-Q282]

Share

Authentic Huawei H19-371_V1.0 Exam Dumps PDF - Feb-2023 Updated

H19-371_V1.0 Dumps Special Discount for limited time Try FOR FREE

NEW QUESTION 260
Regarding the micro-module and fire protection system, which of the following are true? (multiple choice)

  • A. The data center fire host provides passive dry contact signals to the ECC800, and the ECC800 can identify the fire alarm information
  • B. ECC800 can control skylight rollover and fire sprinkler to spray fire gas
  • C. When a fire alarm occurs in the channel, the ECC800 provides an alarm to the data center fire host by providing passive thousand-contact signals.
  • D. ECC800 controllable module and building fire control linkage

Answer: A,B,C,D

 

NEW QUESTION 261
The NetEco management system can provide the temperature cloud map function, which is used to monitor the temperature distribution in the computer room and quickly identify the hot spots in the computer room.

  • A. False
  • B. True

Answer: B

 

NEW QUESTION 262
FusionModule800 version 3.0 supports face recognition ()

  • A. False
  • B. True

Answer: B

 

NEW QUESTION 263
The minimum floor height of the computer room required by FusionModule2000 is 2.6 meters.

  • A. False
  • B. True

Answer: B

 

NEW QUESTION 264
Regarding the adjustable battery of UPS5000-E, when one of the batteries is broken, at least one ( ) battery needs to be removed. Then set the corresponding number of battery cells on the monitoring panel.

  • A. 0
  • B. 1
  • C. 2
  • D. 3

Answer: C

 

NEW QUESTION 265
At which of the following voltages the lead-acid battery is already in a dangerous state ()

  • A. 2.35
  • B. 2.45
  • C. 1.67
  • D. 2.25

Answer: B

 

NEW QUESTION 266
When the NetCol8000-C room-level chilled water intelligent temperature control product is booted, our ( ) model will be used first.

  • A. 190D
  • B. 130D
  • C. 160D
  • D. 150D

Answer: A,B

 

NEW QUESTION 267
UPS5000- has the function of adjustable number of battery cells, to avoid the replacement of gangs caused by a single battery failure, and to solve the problem of difficult maintenance of traditional UPS batteries.
How many adjustable batteries does UPS5000-E (50kVA module) support? ( )

  • A. 30-46
  • B. 32-47
  • C. 30-40
  • D. 32-40

Answer: A

 

NEW QUESTION 268
UPS products such as APM and NR need to be derated at 30 degrees, UPS5000-E does not need to be under 40 degrees ()

  • A. False
  • B. True

Answer: B

 

NEW QUESTION 269
The RS485 expansion card in the ECC500 collector can provide 5 RS485 interfaces, and each interface can provide 12V DC output.

  • A. False
  • B. True

Answer: A

 

NEW QUESTION 270
NetCo15000-C row-level chilled water intelligent cooling product supports return air, supply air, cold aisle, hot aisle and other types of temperature and humidity control ( )

  • A. False
  • B. True

Answer: B

 

NEW QUESTION 271
The number of group controllers for Huawei NetCol series smart cooling products is ()

  • A. 0
  • B. 1
  • C. 2
  • D. 3

Answer: B

 

NEW QUESTION 272
The NetEco management system supports the function of user decentralization and domain division, which can realize that different operation and maintenance personnel can only view the equipment managed by themselves. For example, by assigning permissions, a certain operation and maintenance personnel can only check the equipment information of the computer room of a few outlets. ()

  • A. False
  • B. True

Answer: B

 

NEW QUESTION 273
Which of FusionModule800 require site survey? (multiple choice)

  • A. Mains to Module Cable Length
  • B. Wiring method
  • C. The way of the pipe
  • D. Length between inside and outside machine

Answer: A,B,C,D

 

NEW QUESTION 274
FusionModule800 closed aisle hot and cold aisle are optional

  • A. False
  • B. True

Answer: B

 

NEW QUESTION 275
What are the incoming line methods supported by UPS5000-A-400/500K? ( )

  • A. Compatible with upper and lower incoming lines
  • B. Downstream
  • C. Top entry line

Answer: A

 

NEW QUESTION 276
The cooling capacity of intelligent temperature control products can only be determined when the working conditions are clarified. There are many factors that affect the cooling capacity. For example, when selecting a row-level chilled water intelligent temperature control product, at least information such as ( ) must be specified.

  • A. Return water temperature
  • B. Length of connecting pipe
  • C. Inlet water temperature
  • D. Return air humidity
  • E. Return air temperature
  • F. Altitude

Answer: A,C,D,E,F

 

NEW QUESTION 277
The UPS5000-E has the function of adjusting the number of battery cells, which avoids the failure of a single battery to cause the replacement of the entire group, and solves the problem of difficult maintenance of traditional UPS batteries. May I ask how many cells can be adjusted in the UPS5000-E (50kVA module)? ()

  • A. 30-44
  • B. 30-40
  • C. 32-42
  • D. 32-40

Answer: A

 

NEW QUESTION 278
FusionModule2000 maximum number of counters ()

  • A. 0
  • B. 1
  • C. 2
  • D. 3

Answer: B

 

NEW QUESTION 279
FusionModule2000 integrated UPS has two types of 50K/125K.

  • A. False
  • B. True

Answer: B

 

NEW QUESTION 280
The characteristics of the compressor used by Huawei NetCo15000-A include: ( ).

  • A. No reciprocating motion, less moving parts, high reliability+
  • B. Highest volumetric efficiency, low noise and low vibration
  • C. International famous brand, long life, high reliability
  • D. Safe operation under 3000V voltage.

Answer: A,B,C

 

NEW QUESTION 281
The UPS supports a variety of systems to meet customer application grid scenarios. Which systems does the UPS2000-G 15/20KVA model support? ( )

  • A. Three in and three out
  • B. One in three out
  • C. Single in, single out
  • D. Three in and one out

Answer: A,C,D

 